ADL400 can measure voltage, current, power, 2~31st harmonic and other electricity. It is equipped with standard RS485 communication, multi tariff and pulse output function.
Product Description
Brand:Acrel | Place of Origin:China | Certificate:CE |
ADL400 three phase electronic meter is mainly used to measure three phase active energy in low-voltage networks. It can also measure voltage, current, power and other electricity parameters. It is equipped with multi tariff, pulse output,standard RS485 communication function, which is convenient for users to monitor, collect and manage electricity consumption.
It can be flexibly installed in the distribution box to realize the sub-item electric energy measurement, statistics and analysis of different areas and different loads.The meter meet the related technical requirements of electronic meter in the IEC62053-21、 IEC62053-22 standards.
ADL400 Three Phase Energy Meter
Total active kWh(positive and negative in total),Frozen data
U、I、P、Q、S、PF、F
2~31st voltage and current harmonic
12 digits LCD display,background light
3 keys to set password, communication address, baud rate, multi-tariff, communication protocol
Active pulse output
Adapt 4 time zones, 2 time interval lists, 14 time interval by day and 4 tariff rates
Max demanded kWh and time happened
Frozen data on last 48 months, last90days
RS485 interface,Modbus-RTU,DL/T645-97,DL/T645-07 protocol
Installation:
DIN 35mm
Parameter
Specification | 3 phase 3 wires, 3 phase 4 wires | |
Voltage | Reference voltage | 3×100V、 3×380V、3×57.7/100V、 3×220/380V |
Consumption | <10VA(Single phase) | |
Accuracy class | Error±0.2% | |
Current | Input current | 3×1(6)A, 3×10(80)A |
Consumption | <1VA(Single phase rated current) | |
Accuracy class | Error±0.2% | |
Power | Active, reactive, apparent power, error±0.5℅ | |
Frequency | 45~65Hz(Error±0.2%) | |
Measuring performance | Energy | Active energy(Accuracy class:0.5, 1) reactive energy(Accuracy class 2) |
Clock accuracy | error≤0.5s/d | |
Digit signal | Energy pulse output | 1 active photocoupler output |
Pulse | Pulse Width | 80±20ms |
Pulse constant | 1000impkWh,10000imp/kWh(Correspond with the basic current) | |
Communication | Interface and communication | RS485:Modbus RTU |
Range of communication address | Modbus RTU:1~ 254 | |
Baud rate | 1200bps~19200bps | |
Outline | L*W*H(mm) | 90*72*65 |
Environment | Temperature | Operating:-25~55℃ Storage:-40~70℃ |
Humidity | ≤95%(No condensation) | |
Altitude | <2000m |