Remote monitoring alarm and display device
You are here: Home » Products » Isolated Power Distribution » Medical IT Isolated Power Supply » Remote monitoring alarm and display device

Remote monitoring alarm and display device

AID10 remote and alarm indicators are installed beside the intelligence panel in the operating room so that medical personnel can immediately receive a notification when there is power supply failure.
Availability:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
sharethis sharing button
  • AID10

  • ACREL

Product Description

Overview
Brand:Acrel

Place of Origin:China

Standards:CE

AID series and display device is a remote display and sound and light alarm device by using advanced fieldbus communications technology. Products can display the current insulation resistance,transformer load rate data and other monitoring data of AIM-M series medical intelligent insulation monitoring device real-time. Products emit sound and light alarm signal when system failure occurs. Products are classified according to the installation method and display. The device can be installed on the operaing room or information control pannel of intensive care unit, the medical staff can easily know the status of medical isolated power systems, and the type of fault when the system fails.


AID10 external alarm display device can monitor an AIM-M10 insulation monitor through RS485 communication interface. It has sound and light alarm function and indicator display of insulation, overload, overtemperature and device disconnection.
AID10 is only used with AIM-M10, which is suitable for embedded wall installation.


Specifications

HG9A2442

AID10 Remote Alarm Indicator


● Remote monitoring

● LED indicators:On, Insulation, Overload, Overtemp

● Mute button

● Test button

● Auxiliary power supply: DC24V

● RS485(MODBUS-RTU)

指示
HG9A2533


●With RS485 interface and MODBUS-RTU communication protocol, it can interact with AIM-M10 in real time and realize remote monitoring.

●When there are insulation faults, overload, excessive temperature rise of transformer and wiring faults in the system, AID10 sends out corresponding sound and light alarms, in which sound alarms can be manually eliminated.

●Device self-inspection can be carried out remotely.


安装图


Parameter

Dimension

dimension


Parameter


Power supply Voltage DC24V
Consumption ≤0.6W
Alarm range Insulation 50-999kΩ
Current 14A、18A、22A、28A、35A、45A
Temperature 0~+200℃
Alarm mode Audible and visual alarm
Alarm type Insulation fault,overload,overtemperature,device failure
Communication RS485,Modbus-RTU
Display mode LCD display,128*64 dot array
Dimension 86*86*37.7mm
Cut-out 60*60mm



Previous: 
Next: 

Product Category

QUICK LINKS

PRODUCT CATEGORIES

CONTACT US

  Phone:+86-18702109693
  Email: elena@acrel.cn
  Skype:elena@acrel.cn
  WhatsApp:+8618702109693
  Address: No. 253, Yulv Road, Jiading
       Zone, Shanghai, China
SEND US A MESSAGE
© 2003-2020 All Rights Reserved. Powered by Acrel    
Sitmap    丨    Support by sdzhidian