Availability: | |
---|---|
AID120
ACREL
Product Description
Brand:Acrel | Place of Origin:China | Standards:IEC 60364-7-710:2002 |
AID series and display device is a remote display and sound and light alarm device by using advanced fieldbus communications technology. Products can display the current insulation resistance,transformer load rate data and other monitoring data of AIM-M series medical intelligent insulation monitoring device real-time. Products emit sound and light alarm signal when system failure occurs. Products are classified according to the installation method and display. The device can be installed on the operaing room or information control pannel of intensive care unit, the medical staff can easily know the status of medical isolated power systems, and the type of fault when the system fails.
The remote alarm indicator can be installed next to the intelligence panel in the operating room and in the nurse station. It will send out alarm to notify relevant personnel to investigate and deal with hidden dangers in time.AID120 alarm and display device is designed for visual and audible indication of alarm messages from ACREL medical intelligent insulation monitor AIM-M10,AIM-M100,AIM-M200,and residual current monitor AIM-R100. It meets with the requirement of IEC 60364-7-710:2002.
Specifications
AID120 Alarm And Display Device ● Remote monitoring ● LED indicators:On, Insulation, Overload, Overtemp ● Mute button ● Test button ● Auxiliary power supply: DC24V ● RS485(MODBUS-RTU) |
● When there are insulation faults, overload, excessive temperature rise of the voltage transformer or wiring faults in any of the monitored system, centralized alarm and display instrument can provide corresponding sound and light alarm function, and can manually eliminate the alarm sound.
Parameter
Dimension
Parameter
Power supply | Voltage | DC24V |
Consumption | ≤0.6W | |
Alarm range | Insulation | 50-999kΩ |
Current | 14A、18A、22A、28A、35A、45A | |
Temperature | 0~+200℃ | |
Alarm mode | Audible and visual alarm | |
Alarm type | Insulation fault,overload,overtemperature,device failure | |
Communication | RS485,Modbus-RTU | |
Display mode | LCD display,128*64 dot array | |
Dimension | 172*87*63mm | |
Cut-out | 158.5*74.5mm |