| Availability: | |
|---|---|
ADL3000-E/CT
ACREL
Download
Manual of ADL3000-E:
CE of ADL3000-E:
Product Description
| Brand:Acrel | Place of Origin:China | Certificate:CE |
ADL3000-E/CT three phase CT energy meter is designed for three phase energy measurement on low voltage system. The meter meet the related technical requirements of electronic meter in the IEC62053-21、IEC62053-22 standards.
Rated U and I
AC 3×100V, 3×380V, 3×57.7/100V, 3×220/380V; 3×1(6)A, 3×10(100)A
Accuracy
kWh: Class 0.5S,kVarh:Class 2
Frequency
50/60HZ(Optional),range: 45~65HZ
Installation:
DIN 35mm
Dimension(L*W*H):
127*88*70mm
Outline of transformer
L*W*H:44*43*29.5mm,Aperture:16mm
Communication
RS485(Modbus-RTU)
Display
8 digits LCD display U, I, P, Q, PF, kWh and other energy consumption, Power measure (999999.99kWh)
Pulse output
Pulse output kWh/kvarh
Consumption
<10VA(Single phase)
Switch relay:
Magnetic latching relay
Clock:
≤0.5s/d
Starting current:
Direct connect: 0.004Ib
Connect via CT: 0.001ln
Parameter
| Voltage | Reference voltage | 3*57.7/100V,3*220/380V, 3*1000V,3*380V |
| Reference frequency | 50Hz | |
| Consumption | <10VA(Single phase) | |
| Current | Maximum current | 3×1(6)A,3×10(100)A |
| Starting current | Direct connect:0.004Ib Connect via:0.001In | |
| Consumption | <1VA(Single phase rated current) | |
| Measurement performance | Accuracy of active kWh | Class 0.5S |
| Standards compliant | IEC62053-21:2003 | |
| Pulse | Pulse width | 80+20ms |
| Pulse constant | 400imp/kWh 6400imp/kWh | |
| Communication | Interface | RS485 |
| Protocol | Modbus-RTU | |
| Outline | L*W*H(mm) | 127*88*70 |
| Environment | Temperature | Operating:-25~55℃ Storage:-40~70℃ |
| Humidity | ≤95%(No condensation) | |
| Altitude | <2000m |